Insu – Rope / Rope Type Fire Barrier
Technical Specifications:
Complete range of Insu-Rope products is certified by SIST EN 13501-2:2008+A1:2009 with 4-hours fire resistance rating, which was achieved in SIST EN 1366-4:2006 tests for both vertical and horizontal application.
Insu – Rope / Rope Type Fire Barrier
FIRE PROTECTION |
Working Temperature |
< 750 ° C |
Melting Point |
> 1000 ° C |
Range of Burn - Retardant |
A1 |
Demands for Fire safety |
Extraordinary High |
LOWER THERMAL LOSSES |
Thermic Conductance |
0,035 W/mK -0,040 W/mK |
SOUND PROTECTION |
|
Meets High Requirements |
Application Areas :
Benefits
Insu – Rope can easily be applied in new or reconstructed buildings.
Choosing the right Insu – Rope
The diameter of Insu-Ropes for different joint widths can be seen below;
Joint Width (mm) |
Insu – Rope
Diameter (mm) |
10 |
12 |
15 |
20 |
20 |
30 |
25 |
40 |
30 |
50 |
40 |
60 |
50 |
70 |
60 |
80 |
70 |
90 |
80 |
100 |
90 |
110 |
100 |
120 |
120 |
140 |
130 |
150 |
140 |
170 |
150 |
180 |
180 |
2 pcs x 110 |
200 |
2 pcs x 120 |
250 |
2 pcs x 150 |
Reaction with Water
Rock wool is a non-hygroscopic material and loses its property in case of contact with water. Therefore if there is a water contact risk , to protect the fire barrier water insulation must be applied prior to placing the barrier.